public class ModifySiteDeviceInfoRequest extends AbstractModel
header, skipSign
Constructor and Description |
---|
ModifySiteDeviceInfoRequest() |
ModifySiteDeviceInfoRequest(ModifySiteDeviceInfoRequest source)
NOTE: Any ambiguous key set via .set("AnyKey", "value") will be a shallow copy,
and any explicit key, i.e Foo, set via .setFoo("value") will be a deep copy.
|
Modifier and Type | Method and Description |
---|---|
Boolean |
getBreakerRequirement()
Get Whether there is an upstream circuit breaker?
|
Boolean |
getConditionRequirement()
Get Whether the following environmental conditions are met:
1.
|
Boolean |
getDimensionRequirement()
Get Whether the following dimension conditions are met:
Your loading dock can accommodate one rack container (H x W x D = 94" x 54" x 48").
|
String |
getFiberType()
Get You are using optical fiber type to connect the CDC device to the network Single-mode or multi-mode fibers are available.
|
Long |
getMaxWeight()
Get Maximum weight capacity (KG)
|
Boolean |
getNeedHelp()
Get Whether you need help from Tencent Cloud for rack installation?
|
String |
getOpticalStandard()
Get Optical standard used to connect the CDC device to the network This field depends on the uplink speed, optical fiber type, and distance to upstream equipment.
|
String |
getPowerConnectors()
Get Type of power connector
|
Long |
getPowerDrawKva()
Get Power consumption (KW)
|
String |
getPowerFeedDrop()
Get Whether power is supplied from above or below the rack
|
Boolean |
getRedundantNetworking()
Get Whether redundant upstream equipment (switch or router) is provided so that both network devices can be connected to the network.
|
Boolean |
getRedundantPower()
Get Whether there is power redundancy?
|
String |
getSiteId()
Get Equipment room ID
|
Long |
getUplinkCount()
Get Number of uplinks used by each CDC device (2 devices per rack) when connected to the network
|
Long |
getUplinkSpeedGbps()
Get Uplink speed from the network to Tencent Cloud Region
|
void |
setBreakerRequirement(Boolean BreakerRequirement)
Set Whether there is an upstream circuit breaker?
|
void |
setConditionRequirement(Boolean ConditionRequirement)
Set Whether the following environmental conditions are met:
1.
|
void |
setDimensionRequirement(Boolean DimensionRequirement)
Set Whether the following dimension conditions are met:
Your loading dock can accommodate one rack container (H x W x D = 94" x 54" x 48").
|
void |
setFiberType(String FiberType)
Set You are using optical fiber type to connect the CDC device to the network Single-mode or multi-mode fibers are available.
|
void |
setMaxWeight(Long MaxWeight)
Set Maximum weight capacity (KG)
|
void |
setNeedHelp(Boolean NeedHelp)
Set Whether you need help from Tencent Cloud for rack installation?
|
void |
setOpticalStandard(String OpticalStandard)
Set Optical standard used to connect the CDC device to the network This field depends on the uplink speed, optical fiber type, and distance to upstream equipment.
|
void |
setPowerConnectors(String PowerConnectors)
Set Type of power connector
|
void |
setPowerDrawKva(Long PowerDrawKva)
Set Power consumption (KW)
|
void |
setPowerFeedDrop(String PowerFeedDrop)
Set Whether power is supplied from above or below the rack
|
void |
setRedundantNetworking(Boolean RedundantNetworking)
Set Whether redundant upstream equipment (switch or router) is provided so that both network devices can be connected to the network.
|
void |
setRedundantPower(Boolean RedundantPower)
Set Whether there is power redundancy?
|
void |
setSiteId(String SiteId)
Set Equipment room ID
|
void |
setUplinkCount(Long UplinkCount)
Set Number of uplinks used by each CDC device (2 devices per rack) when connected to the network
|
void |
setUplinkSpeedGbps(Long UplinkSpeedGbps)
Set Uplink speed from the network to Tencent Cloud Region
|
void |
toMap(HashMap<String,String> map,
String prefix)
Internal implementation, normal users should not use it.
|
any, fromJsonString, getBinaryParams, GetHeader, getMultipartRequestParams, getSkipSign, isStream, set, SetHeader, setParamArrayObj, setParamArraySimple, setParamObj, setParamSimple, setSkipSign, toJsonString
public ModifySiteDeviceInfoRequest()
public ModifySiteDeviceInfoRequest(ModifySiteDeviceInfoRequest source)
public String getSiteId()
public void setSiteId(String SiteId)
SiteId
- Equipment room IDpublic String getFiberType()
public void setFiberType(String FiberType)
FiberType
- You are using optical fiber type to connect the CDC device to the network Single-mode or multi-mode fibers are available.public String getOpticalStandard()
public void setOpticalStandard(String OpticalStandard)
OpticalStandard
- Optical standard used to connect the CDC device to the network This field depends on the uplink speed, optical fiber type, and distance to upstream equipment.public String getPowerConnectors()
public void setPowerConnectors(String PowerConnectors)
PowerConnectors
- Type of power connectorpublic String getPowerFeedDrop()
public void setPowerFeedDrop(String PowerFeedDrop)
PowerFeedDrop
- Whether power is supplied from above or below the rackpublic Long getMaxWeight()
public void setMaxWeight(Long MaxWeight)
MaxWeight
- Maximum weight capacity (KG)public Long getPowerDrawKva()
public void setPowerDrawKva(Long PowerDrawKva)
PowerDrawKva
- Power consumption (KW)public Long getUplinkSpeedGbps()
public void setUplinkSpeedGbps(Long UplinkSpeedGbps)
UplinkSpeedGbps
- Uplink speed from the network to Tencent Cloud Regionpublic Long getUplinkCount()
public void setUplinkCount(Long UplinkCount)
UplinkCount
- Number of uplinks used by each CDC device (2 devices per rack) when connected to the networkpublic Boolean getConditionRequirement()
public void setConditionRequirement(Boolean ConditionRequirement)
ConditionRequirement
- Whether the following environmental conditions are met:
1. There are no material requirements or the acceptance standard on site that will affect the delivery and installation of the CDC device.
2. The following conditions are met for finalized rack positions:
Temperature ranges from 41 to 104°F (5 to 40°C).
Humidity ranges from 10°F (-12°C) to 70°F (21°C) and relative humidity ranges from 8% RH to 80% RH.
Air flows from front to back at the rack position and there is sufficient air in CFM (cubic feet per minute). The air quantity in CFM must be 145.8 times the power consumption (in KVA) of CDC.public Boolean getDimensionRequirement()
public void setDimensionRequirement(Boolean DimensionRequirement)
DimensionRequirement
- Whether the following dimension conditions are met:
Your loading dock can accommodate one rack container (H x W x D = 94" x 54" x 48").
You can provide a clear route from the delivery point of your rack (H x W x D = 80" x 24" x 48") to its final installation location. You should consider platforms, corridors, doors, turns, ramps, freight elevators as well as other access restrictions when measuring the depth.
There shall be a 48" or greater front clearance and a 24" or greater rear clearance where the CDC is finally installed.public Boolean getRedundantNetworking()
public void setRedundantNetworking(Boolean RedundantNetworking)
RedundantNetworking
- Whether redundant upstream equipment (switch or router) is provided so that both network devices can be connected to the network.public Boolean getNeedHelp()
public void setNeedHelp(Boolean NeedHelp)
NeedHelp
- Whether you need help from Tencent Cloud for rack installation?public Boolean getRedundantPower()
public void setRedundantPower(Boolean RedundantPower)
RedundantPower
- Whether there is power redundancy?public Boolean getBreakerRequirement()
public void setBreakerRequirement(Boolean BreakerRequirement)
BreakerRequirement
- Whether there is an upstream circuit breaker?Copyright © 2025. All rights reserved.